Continuously Variable Auto Transformers
0.75A - 50A Single & Three Phase Models
 
     
 
SINGLE PHASE FLUSH TYPE MODELS
115V 60Hz
230V 50Hz
Dimensions (in mm)
Model
Current
Model
Current
A
B
E
H
Ø
5F-1A
5A
2F-1
2A
110
92
15
95
7
10F-1A
10A
4F-1
4A
175
146
25
102
10
15F-1A
15A
8F-1
8A
175
146
25
130
10
18F-1A
18A
10F-1
10A
180
155
25
135
10
30F-1A
30A
15F-1
15A
225
176
25
135
11
40F-1A
40A
20F-1
20A
240
205
25
135
11
50F-1A
50A
28F-1
28A
300
238
60
145
13

ENCAPSULATED AUTO-TRANSFORMERS
Model
Output
0-270V
A
B
C
 D 
 E 
F
2N-1A
1A
90
105
105
6
24
11
4N-1A
2A
113.5
126
114
6
25
15
6N-1A
3A
113.5
126
124
6
25
15
10N-1A
5A
165
185
120
8
30
22.5
20N-1A
10A
164
185
143
8
30
22.5
 
A range of high quality compact encapsulated anti-wound variable trasformers designed for panel mounting applications where moisture-proof precision measurement instrumentation is involved. Encapsulation provides additional insulation due to epoxy casting of the transformer windings which also enhances safety of the equiptment.

THREE PHASE OPEN TYPE MODELS 
115V 60Hz
230V 50Hz
Dimensions in mm
Model
Current
Model
Current
A
B
E
H
5F-3A
5A
2F-3
2A
110
92
15
95
4F-3A
10A
4F-3
4A
175
146
25
102
8F-3A
15A
8F-3
8A
175
146
25
130
15F-3A
30A
15F-3
15A
225
176
25
135
20F-3A
40A
20F-3
20A
240
205
25
135
28F-3A
50A
28F-3
28A
300
238
60
145
 

THREE PHASE MODELS
Ganged Assembly of three torroidal coils provide the Three Phase Models and a common coaxial shaft helps to provide continuous control of three phase output.
 
REMOTE CONTROL MODELS
VATs are also available with a stepper Motor bi-directional drive to enable remote control of the output voltage with ‘raise’ or ‘lower’ push button switches.
 
115V AND 230V MODELS
VATs are available for 115V or 230V operation at any line frequency between 47Hz and 63Hz.
 
RATING AND SPECIFICATIONS
All Single Phase VATs are rated for 115V or 230V AC. 50/60Hz single phase supply. Three Phase Models are for 200V or 400V AC. 50/60Hz input and provide variable Three Phase 4 wire voltage output.
The output voltage can be varied smoothly over two ranges :
(i) from zero to full supply voltage (line voltage connection) or
(ii) from zero to approx. 15% high than the supply voltage (Booster Voltage Connector).
As the output voltage is continuously variable, VATs cannot be rated in terms of KVA but are rated in terms of current that can be drawn from the output. The rating assigned to a VAT generally indicates the max. output current that can be drawn at any voltage, over the entire range. VATs can also be supplied for non-standard input.
 
CONSTRUCTION
Single Phase VATs are generally supplied in two types of construction, one is a portable type with sheet metal enclosure. For mounting them flush or back of panel, or inside a cubicle, they are supplied without any enclosure.
 
MAINTENANCE
When operated within its rated capacity, VATs has long life. For protection, it is advised to use a fast acting fuse at the output and a slow acting fuse at the input.
 

  BACK