80KVA to 150KVA UPS Systems (3Ph - 3Ph) - MP Series
 
     
 
Features   MP Series UPS
  • 80-150KVA in 4 Ratings
  • Sophisticated High Specification On Line Configuration with Optional Static Switch
  • State of the Art IGBT Based Pulse Width Modulation (PWM) Technology to Reduce Harmonic Distortion and Increase Both Crest Factor Tolerance and Dynamic Stability
  • Higher Efficiency of Operation Means Crotech UPS has Significantly Lower Running Costs than Leading Competitors
  • Continuously Delivers Full Rated Power at Ambient as high as 45ºC
  • Parallel Operation of UPS
  • Comprehensive Indication of Normal and Fault Conditions
  • Excellent Unbalanced Line & Load Performance
  • Compatible with Sealed Maintenance Free Battery as well as Tubular Lead Acid Batteries
  • Compact Cabinet & Ultra Light Weight
  • Easy Installation with Wheels for Manoeuvreability and Front Terminal Box
  • Optional Remote Status Panel
    

Technical Specifications
MODEL
HP3080
HP3100
HP3120
HP3150
RATED POWER (at PF 0.8)
80KVA
100KVA
120KVA
150KVA
INPUT
Voltage Nominal
             Range
400V AC
340V AC to 460V AC.
Frequency Nominal
                  Range
50Hz.
47 to 53Hz.
Phase
Three Phase, 4 Wire.
AC to AC Efficiency
>88% peak
>89% peak
OUTPUT
Power Max.
80KVA/64KW
100KVA/80KW
1200KVA/96KW
150KVA/120KW
Current
116 Amps.
145 Amps.
174 Amps.
217 Amps.
Voltage
400V AC.
Voltage Regulation
±1% Typical.
Frequency
50Hz.
Frequency Stability
±0.05%.
Phase
Single Phase.
Waveform
Sinewave.
Total Harmonic Distortion
Less than 2% with Linear Load.
TRANSIENT RESPONSE
(100% Load Step)
Less than ±5%.
RESPONSE TIME
Less than 60 milli-seconds to reach within ±2%.
LOAD POWER FACTOR RANGE
Unity to 0.8 Lag within specified max. output power ratings.
OVERLOAD RATING a) 1/2 Hour
b) 10 Seconds
c) 10 Cycles
120%
150%
200%
  
PROTECTIONS a) Input Over/Under Voltage
b) Phase Fail
c) Overload at the Output
d) SOAR Protection for IGBTs
e) Output AC Over/Under voltage
f) High Speed Fuses for Semi-Conductor Devices
g) Snubber Circuits for Power Semi-Conductor Devices
INDICATIONS a) Mains On
b) Inverter On
c) Battery on Charge
d) Mains Over/Under Voltage
e) Phase Fail
f) Low Battery Imminent
g) Battery Over/Under Voltage
h) Inverter Over/Under Voltage
i) Inverter Overload
j) Overheat
AUDIBLE ALARM
For Conditions from (d) to (j) a Local Buzzer operates.
REMOTE INDICATIONS
A potential free contact is provided for fault indications and alarm.
COMPUTER INTERFACE
RS-232 (Optional).
METERING 16 x 2 LCD to measure the following :
a) AC Input/Output Voltage per Phase
b) Load percentage
c) DC Voltage
d) Battery percentage
e) Output Frequency
BATTERY
Nominal Voltage
384V DC.
Type
Sealed maintenance free/tubular lead Acid Battery.
Standby Period
(Full Load at 0.8 PF)
30 Minutes (can be increased upto 2hrs and extended further on request).
GENERAL
Operating Temperature
0 to 45ºC.
Storage
-20ºC to +65ºC.
Finish
Cool Grey Shade No.5-C & 1-C/DA Grey IS632.
Relative Humidity
Non Condensing
0 to 95%.
Enclosure Protection
IP20.
Dimensions  HEIGHT
                    WIDTH
                    DEPTH
1800 mm
1000 mm
800 mm
1900 mm
1000 mm
800 mm
2000 mm
1100 mm
800 mm
2200 mm
1200 mm
900 mm
Weight
830 Kgs.
1000 Kgs.
1100 Kgs.
1300 Kgs.
OPTIONAL STATIC SWITCH
Transfer Time a) Less than 5 milli-seconds from inverter to mains.
b) Less than 5 milli-seconds from mains to inverter.
Indications a) Aux. Supply On
b) Load on Inverter
c) Load on Aux. Supply
d) Manual Bypass On
 

  BACK